How far can you run a 12/2 wire on a 20 amp circuit?

Twelve-two on a 20 amp circuit runs about 50 feet at a full 20 amp load before drop passes the recommended 3 percent, and roughly 100 feet at a 10 amp load. The code sets no hard length limit; the volts do.

Real receptacle circuits rarely see sustained full load, which is why 70 or 80 foot bedroom runs on 12/2 work fine in practice.

For a known steady load at distance, a detached shed compressor for instance, size by the actual amps: at 16 continuous amps, 12 gauge gives out near 60 feet and 10 gauge takes over.

Rule of thumb worth keeping: one size up per additional 100 feet.

The 20 amp length calculator gives the exact cutover distance for your load.

WireGaugeCalc runs every NEC calculation in one free app, with the code article cited on each result.